XM31-915-HP - 10051330
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V2.06.0
Major Alarm
OK
Minor Alarm
String A balancing: check battery 3
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
122.20
V
Current
7.99
A
Power
804
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
9,807
Wh
1
Output
Voltage
85.73
V
Power
632
W
Apparent Power
727.84
VA
Frequency
59.98
Hz
Percent Load
56.60
%
Output Setting
90 V
Output Regulation
Coarse override
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
8.49
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.70
V/cell
Reduced Peak Mode
Enable
Total Standby Events
35
Time Since Last Standby Event
18d 19h:02m
Time in Last Standby Event
0d 0h:12m
Total Time in Standby
786
min
Standby Events Since Reset
14
Time in Standby Since Reset
384
min
Time Since Reset
388
day(s)
Total Run Time
388
day(s)
Transformer Run Time
388
day(s)
Total Downtime
0d 0h:00m
Oil Cap Lifespan Consumed
13.0
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
45
day(s)
Test Duration
30
min
Test Interval
56
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2023 EnerSys. All Rights Reserved.
www.alpha.com
|
www.enersys.com
Close