XM31-915-HP - 10051330
Batteries
 
 

Alarms
 

Battery
 

Batteries
Battery String Voltage 40.29 V
Estimated Runtime At least 8 hours
Battery Life Remaining Over five years
Battery Balancing Check battery
Balancing String String A
Battery System Configuration 2 strings of 3 batteries each
Battery Temperature 28 °C
82 °F
  1 2 3 Balancing
String A 14.08 V 13.71 V 12.59 V Check battery 3
String B 13.48 V 13.51 V 13.41 V Moderate
Battery Charging
Charger Mode Float
Current Charger Mode Time 3,331 min
Charger Current 0.36 A
Charger Current Limit 10.50 A
Charger Enable Yes
Configuration
Technician ID 0
24 Hour Battery Refresh No
Battery Model 4.0HP
Accept Voltage 2.35 V/cell
Float Voltage 2.25 V/cell
Refresh Voltage 2.45 V/cell
Battery Capacity 114 Ah
Temperature Compensation 4.00 mV/cell/°C
HP Battery Rest Mode Yes
Battery String Detect Auto
Number of Battery Strings 2
Heater Mat Installed No
Conductance
Last Conductance Measurement  
  Last Adjusted Conductance Measurement Manufactured Date
String A Battery 1 0 S(℧) 2022-08
String A Battery 2 0 S(℧) 2022-08
String A Battery 3 0 S(℧) 2022-08
String B Battery 1 0 S(℧) 2022-08
String B Battery 2 0 S(℧) 2022-08
String B Battery 3 0 S(℧) 2022-08

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.